Logo
Technical Specifications
Medium

4120.40M/.41M: Water-based 

4121.40M/.41M: Oil-based

Sensor Data
Measuring range

4120.40M/.41M: 0 - 20 cm/s to 0 - 300 cm/s, cont. adjust 

4121.40M/.41M: 0 - 30 cm/s to 0 - 300 cm/s, cont. adjust

Set-point range

ca. 15 % - 90 % of measuring range setting

Medium temperature

-20 °C to +80 °C

Ambient temperature

-20 °C to +70 °C

Pressure

max. 100 bar (1000 Kpa)

Response time

4120.40M/.41M: 2 - 10 sec., according to range setting 

4121.40M/.41M: 2 -15 sec., according to range setting

Linearity deviation

< 5 % (See note 1 + 2) most favourable straight line related to the final value

Repeatability

< 2 %

Hysteresis

ca. 10 %

Mechanical data
Protection class

IP 67

Material housing

stainless steel AISI 303

Material of sensor probe

Stainless steel AISI 303 or equivalent (other material on request)

Thread

G ½ “ BSP, alt. ½ “ 14 - NPT

Electrical connection

2 m oilflex cable, 6 x 0.5 mm²

Electrical data
Operating voltage

18 - 30 VDC

Switching current / Contact load

 ≤ 5 A, 120 VAC / ≤ 3A, 250 VAC / 5A, 150W at VDC

Initial operation

approx 10 sec. after connection of power

Electrical output, flow

Relay with potential free contact

Flow < set-point

4120.40M/.41M: .40

4121.40M/.41M: .41

LED, green

4120.40M/.41M: off

4121.40M/.41M: off

Output relay

4120.40M/.41M: activated

4121.40M/.41M: not activated

Notes

1) data relate to water
2) calibrated with insulation oil type "Shell Diala S4 ZX-I"

To top